LGSCentral Cooling Plant

LGS Series Large Chiller

High-capacity central cooling · efficient, stable, dependable

High-capacity central cooling plant for production lines and large process-cooling duties.

  • Cooling capacity52~825kW
  • Temperature range5℃ / -25℃ – RT
  • Control systemPLC control
  • HMI7-inch colour touchscreen
  • CommunicationRS485 Modbus RTU
LGS Series Large Chiller

Overview

The LGS large chiller pairs screw compressors with a PLC controller for precise control and real-time display. Two bands are offered, 5℃–RT and -25℃–RT, covering 52 to 825 kW, with DN50–DN150 chilled- and cooling-water connections. The powder-coated enclosure sits on a channel-steel base as an integrated skid, suited to central plant and large process-cooling duties.

Features

  • 01Energy-efficient, stable and dependable
  • 02Modular design for flexible combination
  • 03Suited to large process-cooling duties
  • 04Comprehensive unit protection and phase monitoring

Typical Applications

  • Central cooling for production lines
  • Process chilled-water systems
  • Large cooling plant for pharma and chemical sites
  • Process cooling in manufacturing workshops

Working Principle

Fill portBuffer tankLevel gaugeCirculation pumpEvaporatorUser equipmentTSupply temp.TReturn temp.CompressorCondenserFilter drierExpansion valve
※ Note: the flow diagram is simplified and may differ from the actual unit.

Model Designation

DLSB0.5WN
  1. 1. Product series code
  2. 2. Temperature code: A -10℃–RT, B -25℃–RT, C -40℃–RT; 5℃–RT is not marked
  3. 3. Capacity code: cooling capacity at 5℃ above the minimum outlet temperature, e.g. 0.5 kW at -20℃. For industrial and precision chillers it is the capacity at a 20℃ outlet; for screw chillers it is the compressor code
  4. 4. Condensing: W for water-cooled; air-cooled is not marked
  5. 5. Non-standard code: see the non-standard code rules; omitted if not required

Specifications

Data taken from the GPTECH product catalogue. Contact us for other models or custom specifications.

SpecificationsLGS Series 5℃–RT

ModelLGS-100WLGS-140WLGS-180WLGS-230WLGS-300WLGS-370WLGS-470WLGS-580WLGS-710W
Main applicationProcess cooling source for pharmaceutical, chemical and machinery production
Temperature range5℃–RT
Cooling capacity kW20℃105146191255325410545680825
5℃85120155210270340450560680
Compressor HP3141556989108141175208
Chilled waterFlow m³/h17253245557090110135
Port sizeDN50DN65DN65DN80DN80DN100DN125DN125DN150
Cooling waterFlow m³/h223342607090120140175
Port sizeDN65DN65DN80DN100DN100DN125DN125DN150DN150
Control systemPLC controller for precise control and real-time temperature display
Controlled variableChilled-water outlet temperature; external tank temperature optional
CommunicationRS485 interface as standard, Modbus RTU protocol
External inputsExternal temperature sensor port, USB data port
Temperature feedbackPT100 feedback on the heat-transfer medium (inlet and outlet temperature)
HMI7-inch colour touchscreen, Chinese/English UI, intuitive operation, displays and logs temperature curves and test data
ProtectionReal-time status display and automatic fault diagnosis with multi-level alarms: compressor overload, high/low refrigerant pressure, oil pressure differential, water cut-off, over-current, over-temperature, temperature module fault, under/over voltage, phase loss and phase sequence.
RefrigerantTypeR22/R407C
Charge kg18.5253342556585105125
Dimensions cm235×65×130245×65×130255×70×135265×75×140275×85×145305×85×150310×95×155330×105×170350×110×175
Unit weight kg8309501100155018502050255029503400
Operating weight kg91510501200175020502250280032503700
EnclosurePowder-coated cold-rolled steel panels, channel-steel base, integrated assembly
Power supply ph/v/Hz3/380/50

※ Notes

  1. Cooling capacities are based on 20℃ cooling-water inlet temperature; air-cooled units at 20℃ ambient.
  2. Flow and head figures apply to water at 20℃; pump performance varies with the density and temperature of the medium.
  3. Only part of the product range is listed. For other models or customised requirements please contact our sales team. Specifications are subject to change without notice.

Need selection advice for the LGS?

Send us your temperature, heat load and flow requirement — an engineer will reply within one working day